Performance characteristics:
● Signal output: RS-485 (Modbus/RTU protocol).
● Easy to connect to PLC, DCS, industrial control computer, universal controller, paperless recording instrument or touch screen and other third party equipment.
● Double high impedance differential amplifier, strong anti-interference, fast response speed.
● ORP probe, the internal reference fluid exudes very slowly from the microporous salt bridge at a pressure of at least 100 kpa (1Bar), with positive exudation for more than 20 months.
● Electrode life is longer than ordinary industrial electrode.
● Easy installation: 3/4NPT pipe thread, easy to sink or mount in pipes and tanks.
● IP68 protection grade.
Mode |
DO-D160 |
Principle of measurement |
Fluorescence method |
Range |
0~20mg/L(0~200% saturation,25℃) |
Resolution |
0.01mg/L,0.1℃ |
Accuracy |
±2% of the measured value, or ±0.3mg/L, whichever is greater |
Temperature compensation |
Automatic Temperature compensation (Pt1000) |
Output mode |
RS-485 bus, Modbus-RTU protocol |
Working condition |
0~45℃、<0.2MPa |
Storage temperature |
-5~65℃ |
Installation mode |
Immersion installation |
Cable length |
5 meters, other lengths can be customized |
Power consumption |
<0.5W |
Power supply |
12~24VDC ±10% |
Protection class |
IP68 |
Calibration |
Two-point calibration |
Fluorescent cap life |
Guaranteed use for one year (normal use) |
Sensor shell material |
POM and 316L stainless steel |